您当前的位置:首页ProductsMonitoring
Wr-cems3000cd continuous monitoring system for flue gas emission (condensation method)
Wr-cems3000cd continuous monitoring system for flue gas emission (condensation method)
详细说明:

Instructions:

WR - CEMS3000CD continuous flue gas emissions monitoring system (CEMS) by the smoke and dust monitoring subsystem, gaseous pollutants monitoring subsystem and the parameters of the flue gas monitoring subsystem, system control and data acquisition processing subsystem of four basic parts. The parameters such as SO2, NOx, O2, dust, temperature, pressure and flow rate in the gas can be monitored, and the parameters such as HCl, HF, CO, CO2 and humidity can be extended for specific occasions. The measured gas enters the analysis and measurement module of micro-heat-tracing gas (DOAS and TDLAS) through the sampling probe dedusting, the sample of the heat tracing tube, and the rapid dewatering and cooling of the secondary condensation. Dry measurement has effectively solved the technical problems such as large fluctuation of data measurement caused by large humidity changes such as refuse incineration.

specifications

SO2 (0 to 20 parts per million (PPM) ~ (0-100%)

Size: 800 mm * 600 mm * 2000 mm

NOx (0 to 20 parts per million (PPM) ~ (0-100%)

Weight: about 250kg

O2:0 ~ 25%

With heat pipe, probe temperature: 120 ℃ ~ 180 ℃

Humidity: 0 ~ 40%

Protection grade: cabinet IP42, other IP65

Dust: (0-50mg/m3) ~ (0-50g/m3)

Power supply: 220 vac

Flow rate: 0 ~ 40m/s(customizable)

Power: 2500 w

Temperature: 0 ~ 300 ℃ (customizable)

Working temperature: - 10 ℃ ~ + 40 ℃

Pressure: -10kpa ~ +10kPa(customizable)

Working humidity: 0-95%RH(no condensation)

The characteristics of

Secondary condensation can quickly remove water and cool down, reduce gas and water contact time, and reduce SO2 loss

The analyzer adopts micro-heat tracing technology to reduce the maintenance cycle of the measuring pool

Fast loop sampling pump sampling, fast response time

Multi-stage filtration water removal, dust removal, high reliability

application

Monitoring and process control of exhaust emissions from coal-fired power plants, garbage power plants, cement plants, glass factories, lime factories, ceramics factories, sintering, coke ovens, desulfurization and denitrification processes

CONTACT

Telephone: 024-24143092

Fax: 024-24121856   Technical support 

telephone number: 24808757,24810226

Website: http://sywaretech.com    